0dcbdbc409719128.tex
1: \begin{abstract}
2: This paper investigates the chattering and deadlock behaviors of
3: the proportional-integral (PI) controller with an anti-windup (AW)
4: limiter recommended by the IEEE Standard 421.5-2016.
5: Depending on the simulation method, the controller may enter a 
6: chattering or deadlock state in some combinations of parameters and inputs.
7: Chattering and deadlock are analyzed in the context of three numerical
8: integration approaches: explicit partitioned method (EPM),
9: execution-list based method (ELM), and 
10: implicit trapezoidal method (ITM). This paper derives the
11: chattering stop condition for EPM and ELP, and
12: analyzes the impacts of step size and convergence tolerance for
13: simultaneous method. The deduced chattering stop conditions and 
14: deadlock behavior is verified with numerical simulations.
15: \end{abstract}