1: \begin{abstract}
2: In Part~I, a method for the \emph{Harmonic Power-Flow} (\HPF) study of three-phase power grids with \emph{Converter-Interfaced Distributed Energy Resources} (\CIDER[s]) is proposed.
3: The method is based on generic and modular representations of the grid and the \CIDER[s], and explicitly accounts for coupling between harmonics.
4: In Part~II, the \HPF method is validated.
5: First, the applicability of the modeling framework is demonstrated on typical grid-forming and grid-following \CIDER[s].
6: Then, the \HPF method is implemented in Matlab and compared against time-domain simulations with Simulink.
7: The accuracy of the models and the performance of the solution algorithm are assessed for individual resources and a modified version of the \CIGRE low-voltage benchmark microgrid (i.e., with additional unbalanced components).
8: The observed maximum errors are 6.3E-5~p.u. w.r.t. voltage magnitude, 1.3E-3~p.u. w.r.t. current magnitude, and 0.9~deg w.r.t. phase.
9: Moreover, the scalability of the method is assessed w.r.t. the number of \CIDER[s] and the maximum harmonic order ($\leqslant$25).
10: For the maximum problem size, the execution time of the \HPF method is 6.52~sec, which is 5 times faster than the time-domain simulation.
11: The convergence of the method is robust w.r.t. the choice of the initial point, and multiplicity of solutions has not been observed.
12: \end{abstract}
13: