1: \begin{abstract}                          % Abstract of not more than 200 words.
2: The traditional secondary frequency control of power systems restores nominal frequency by steering \emph{Area 
3: Control Errors} (ACEs) to zero. Existing methods
4: are a form of integral control with the characteristic that 
5: large control gain coefficients introduce an overshoot and small ones result in a slow 
6: convergence to a steady state. In order to deal with the large frequency
7: deviation problem, which is the main concern of the power system integrated with a
8: large number of renewable energy, a faster convergence is critical. 
9: In this paper, we propose a secondary frequency control method
10: named \emph{Power-Imbalance Allocation Control} (PIAC) to restore the nominal frequency with a minimized control cost,
11: in which a coordinator estimates the power imbalance and dispatches the control inputs to the controllers
12: after solving an economic power dispatch problem. The power imbalance estimation converges exponentially in PIAC, both
13: overshoots and large frequency deviations are avoided. In addition, when PIAC is implemented in a multi-area controlled network,
14: the controllers of an area are independent of the disturbance of the neighbor areas. 
15: A Lyapunov stability analysis shows that PIAC is locally asymptotically stable and simulation results illustrates that it effectively
16: eliminates the drawback of the traditional integral control based methods. 